Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Helvetia Shop 12/19/2017
|
|
- Bathsheba Cummings
- 5 years ago
- Views:
Transcription
1 Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Helvetia Shop 12/19/2017 Winning Bid PERMIT FEES, FORMS, PLANS and NOTIFICATIONS Secure all necessary state and local permits for entire project including removal and disposal of old underground tanks, and complete installation of new above ground system, including canopy. Yes Yes Yes Yes Notification to inspectors, and completion of required paperwork. Yes Yes Yes Yes Draft a SPCC plan Yes Yes Yes Yes REMOVAL & DISPOSAL Remove and dispose existing dispensers and concrete, and light fixture. Yes Yes Yes Yes Remove and dispose existing below ground 10,000 gallon, single wall, fiberglass tank and plumbing. Yes Yes Yes Yes Provide at least two (2) 55 gallon drums for disposal of non-hazardous in-tank sludge disposal. Disposal and cost is bidders responsibility Yes $230 per additional drum Yes $475 per additional drum Yes $380 per drum Yes $475 per add. drum Specify cost of additional drums Backfill site to grade, providing 12 gravel top base, and compact Yes Yes Yes Yes Provide assessment and documentation of soil contamination and Guidance. Yes Yes Yes Yes Disconnect existing Fuel Master terminal and save for installation on new fueling system. Yes Yes Yes Yes INSTALLATION Unload and set one (1) 12,000 gallon and one (1) 5,000 gallon aboveground double wall UL-142 tanks. Yes Yes Yes Yes Install new above ground tanks. Yes Yes Yes Yes Provide labor, tools, and equipment to plumb and install all proposed equipment. Yes Yes Yes Yes Provide and install all necessary decals. Yes Yes Yes Yes Setup, startup, testing, and calibration of equipment. Yes Yes Yes Yes Furnish and install (1) fire extinguisher with cabinet. Yes Yes Yes Yes Train owner on proper equipment use and maintenance. Yes Yes Yes Yes Submit warranty paperwork to manufacturers. Yes Yes Yes Yes Install existing Fuel Master terminal. Change terminal configuration from a single product dual dispenser, to a dual product, dual dispenser. Yes Yes Yes Yes 1
2 ABOVE GROUND TANKS (AST) One (1) 12,000 gallon UL142 double wall vertical tank 12 diameter 14 tall, painted white, including ladder, railing, or any fall protection for tank top inspections, securable to prevent unauthorized access. (Diesel) Yes Yes Yes Yes One (1) 5,000 gallon UL142 double wall vertical tank 9 diameter 10 6 tall, painted white, including ladder, railing, or any fall protection for tank top inspections, securable to prevent unauthorized access. (Gas) Yes Yes Yes Yes GASBOY DISPENSING EQUIPMENT Two (2) Gasboy commercial 9853KXTW2 electric twin dispenser, (2) product (Diesel and No-Lead) side load, standard flow single pulse unit. Black top and sides with white doors. Yes Yes Yes No Make and Model of dispensers Gasboy 9853KXTW2 Gasboy 9853KXTW2 Gasboy 9853KXTW2 Bennett 3722-SNR Specify dispenser warranty 1yr parts & labor-additional 5yr avail. 1 Yr 1 Yr 1 year Include No Smoking, Stop Engine, and Octane decals Yes Yes Yes Yes EMERGENCY VALVES 2 Double poppet emergency valves Yes Yes Yes Yes GAS HOSES, NOZZLES, SWIVELS Two (2) ¾ Automatic nozzles, breakaway connectors, swivel connectors, and 5/8 x 8-1/2 hoses. Yes Yes Yes Yes DIESEL HOSES, NOZZLES, SWIVELS Two (2) 1 Automatic nozzles, breakaway connectors, swivel connectors, and 1 x 18 hoses. Yes Yes Yes Yes Two (2) High hose retractors which include a hose bun, cables, base and Clamp for hose. Yes Yes Yes Yes CENTERON TANK LEVEL MONITOR Remove existing Veeder Root TLS350 unit and probes Yes Yes Yes Yes Install new tank radar level sensor and analog controller Yes Yes Yes Yes Set up online monitoring to coincide with our existing New London and Larrabee site which also uses Centeron system Yes Yes Yes Yes Connect Centeron system via internet connection Yes Yes Yes Yes SUBMERSIBLE EQUIPMENT One (1) 1 1/2 H.P. Red Jacket submersible pumps for diesel. Yes Yes Yes Franklin Fueling Yes One (1) ¾ H.P. Red Jacket submersible pump for No-Lead Yes Yes Yes Franklin Fueling Yes 2
3 CANOPY Erection of a four post canopy (45 x 15 ) to cover dispensing equipment and vehicles at dispensers. Clearence Subset 1 6 Yes Yes Yes Yes Canopy to include three (3) LED lights with photo eye. Yes Yes Yes Yes Loads per state and local codes. Yes Yes Yes Yes Footings installed per canopy specifications/state and local code Yes Yes Yes Yes Includes all state and local permits Yes Yes Yes Yes External downspouts, draining canopy to the surface Yes Yes Yes Yes Width spacing 3, 9, 3 Yes Yes Yes Yes Length spacing 15, 15, 15 Yes Yes Yes Yes CONCRETE and CRASH PROTECTION One (1) concrete tank pad to support vertical tank system and equipment. 20 x 54 x 8 thick Yes Yes Yes Yes Tank pad forms must be set at an elevation of 0.2 feet less than Designated benchmark marked with pink paint on the LR corner of the Scale platform as viewed from the road. After forms are set, prior to pouring concrete, proper elevation must be verified by Highway Dept. personnel. 24 hours prior notice of setting forms must be given. Yes Yes Yes Yes Two (2) concrete fueling pads, 15 x 54 x 8 thick. Yes Yes Yes Yes Fueling pads must a maximum of 1 percent slope down and away from Center tank pad. Yes Yes Yes Yes Twenty six (26) 6 guard posts to protect equipment. Yes Yes Yes Yes 16 W x 30 L x 6 H cyclone security fence with one (1) 3 wide lockable gate to secure tanks and fill box. Yes Yes Yes Yes ELECTRICAL Two (2) Dispensers Yes Yes Yes Yes Two (2) Submersibles Yes Yes Yes Yes Two (2) Solenoid Valves Yes Yes Yes Yes One (1) Card System Yes Yes Yes Yes One (1) Tank Level Monitor Yes Yes Yes Yes Two (2) Probes Yes Yes Yes Yes One (1) Overfill Alarm(s) & Acknowledgement Switch Yes Yes Yes Yes Three (3) Canopy Lights Yes Yes Yes Yes One (1) Emergency Shut Off Switch Yes Yes Yes Yes Surge protection hard wired at source of power to protect fuel dispensing equipment Yes Yes Yes Yes 3
4 TANK EQUIPMENT and PIPING One (1) 15 gallon ground level spill containers, 3 ball valve, 3 sing check valve, 3 male cam adaptor, and 3 fill cap for each product Yes Yes Yes Yes Two (2) Morrison # AV 3 overfill valve or Two (2) Morrison #419 3 aluminum drop tube or comparable. Yes Yes Yes Yes One (1) 3 Updraft vent and riser pipe. Yes Yes Yes Yes One (1) 3 Pressure vacuum vent and riser pipe. Yes Yes Yes Yes Four (4) 8 Emergency vents. Yes Yes Yes Yes Two (2) OPW 200TG mechanical tank gauge or Two (2) Morrison # /2 Anti-siphon solenoid valve or Two (2) OPW TGTA Tank bung gauge/alarm combo fitting or Two (2) OPW 44TA-LLFS 36 Liquid-Level float switch or One (1) OPW 444TA-0100 Four signal tank alarm or 3 Schedule 40 black pipe for product fill. Yes Yes Yes Yes 2 Schedule 40 black pipe for product supply. Yes Yes Yes Yes One (1) Aluminum emergency pump shut-off sign. Yes Yes Yes Yes One (1) Aluminum tank alarm sign Yes Yes Yes Yes Set of NFPA 704 and tank ID decals as required. Yes Yes Yes Yes 4
5 PRICE PROPOSAL TOTAL BID COST $174,950 $194, $189, $244,650 PROJECT COMPLETION DATE: 90 Days ARO 5/30/2018 4/30/2018 6/15/2018 5
6 6
Installation Instructions for. Thrifty King CT Series Fountains
Installation Instructions for Thrifty King CT Series Fountains Congratulations, you have just purchased the finest watering fountain on the market. This unit is built to give you excellent service when
More informationInstallation Instructions for. Thrifty King CT Series Fountains
Installation Instructions for Thrifty King CT Series Fountains Congratulations, you have just purchased the finest watering fountain on the market. This unit is built to give you excellent service when
More informationINVITATION TO BID PURCHASING DEPARTMENT P.O. BOX N. PATTERSON ST. VALDOSTA, GEORGIA
INVITATION TO BID PURCHASING DEPARTMENT P.O. BOX 1349 300 N. PATTERSON ST. VALDOSTA, GEORGIA 31601 #LC-2017-6303 FOR: Equipment for Engine 54 OPENING DATE: August 1, 2016 TIME: 10:00 am EST AMY WOODS,
More informationDEF DISPENSING SOLUTIONS
DEF DISPENSING SOLUTIONS HEAVY-DUTY PORTABLE PACKAGES Model 550 014 Heavy-duty portable air operated package for 55 gallon drum with dispense hose includes 1305 three wheel heavy-duty cart with 2845 ClassicFlo
More informationTents & Membrane Structures Information Packet
Tents & Membrane Structures Information Packet South Metro Fire Rescue Authority Community Safety Services Division Life Safety Bureau 9195 E. Mineral Ave. Centennial, Colorado 80112 Tel: (720) 989-2230
More informationMarin County Fire Department. Fire Protection Standard 119. Tents and Awnings
Page: 1 7 Scope: These standards shall apply to any temporary membrane structure, tent, or canopy, in accordance with the California Code Regulations (CCR) Title 19 and California Fire Code (CFC). Temporary
More informationTENTS, CANOPIES AND TEMPORARY MEMBRANE STRUCTURES
INFORMATION BULLETIN TENTS, CANOPIES AND TEMPORARY MEMBRANE STRUCTURES Code Reference: Title 19 California Code of Regulations California Fire Code (CFC), 2001 Edition, Article 32 California Building Code
More informationPermit Application Requirements For Temporary Tents, and Membrane Structures
CTY OF PAM DESERT Building & Safety Department Permit Application Requirements For Temporary Tents, and Membrane Structures F O R M A T O A B U E T Revised 1-30-14 73510 Fred Waring Drive Palm Desert,
More informationPetroleum Equipment Catalog Evolution
Revision Date: August 2018 Petroleum Equipment Catalog Evolution Service Station Equipment Table of Contents Underground Storage Tank Equipment A0030/A0089 Fill Adapters 5-6 A0097 Fill Caps 7 A0076 Vapor
More informationUSE OF TENTS Guide. Frederick County Fire and Rescue Services Division. Office of the Fire Marshal
Frederick County Fire and Rescue Services Division 5370 Public Safety Place Frederick, MD 21704 301-600-1479 USE OF TENTS Guide Office of the Fire Marshal Guidelines for the Use of Tents The following
More informationPARTS MANUAL. For AST and ATU Model Tuckunder Liftgates
A N T H O N Y L I F T G A T E S, I N C. PARTS MANUAL For AST and ATU Model Tuckunder Liftgates MODELS AST-1500-SF AST-2000-SF AST-2500-SF AST-3000-SF ASTL-1800-SF ASTL-2500-SF ATU-1800-SF ATU-2500-SF ATU-3000-SF
More informationOW LEE CASUAL FIRESIDE Q&A
Are the fire pits certified? All of our units are lab tested and certified by Labtest Certification, we are ANSI and CSA approved for the United States and Canada. The Casual Fireside Fire Pits BTU rated?
More informationFor draining expansion tanks, other liquid storage vessels.
Plumbing Specialties 26-100 & 26-300 SERIES COMPRESSION GAUGE COCKS For draining expansion tanks, other liquid storage vessels. 26-100: rated up to 125 psig 26-300: soft metal seat/stuffing box rated up
More informationService Station Equipment
Service Station Equipment Table of Contents Service Station Equipment Underground Storage Tank Equipment A0030/A0089 Fill Adapters 5-6 A0097 Fill Caps 7 A0076 Vapor Adapters 8 A0099 Vapor Caps 9 A0060
More informationFlammable and Combustible Liquids. OSHA Office of Training and Education 1
Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and
More informationEXPLOSIONADO DE PARTES
EXPLOSIONADO DE PARTES LAVADORA FRONTAL Modelo: Marca TOP AND CABINET PARTS Mexico S.A de C.V. 1/12 CJG R e f Marca Descripción TOP AND CABINET PARTS C a n t Numero de Parte 2 Top 1 8540716 3 Cabinet 1
More informationAutomated Tiki Torch Installation Instructions
Automated Tiki Torch Installation Instructions Automated Tiki Torch with Poles (Exploded View) 14 Automated Tiki Head 6 8 Tiki Pole (Powder Coated Aluminum or Faux Bamboo Pole) 18 Base Pole (Powder Coated
More informationSafety,Monitoring and Accessories
S TATEBOURNE cryogenics Safety,Monitoring and Accessories Temperature Monitoring Cryogenic Accessories Protective Equipment Personal Accessories Hoses and Adapters Liquid Level Control Laboratory Safety
More informationREPORT ON TRAIN DERAILMENT IN PITTSBURGH TUNNEL WEDNESDAY OCTOBER 10, 2001 By Thomas Edward Fox
REPORT ON TRAIN DERAILMENT IN PITTSBURGH TUNNEL WEDNESDAY OCTOBER 10, 2001 By Thomas Edward Fox During the early morning hours of Wednesday, October 10, 2001, twelve hopper rail cars traveling on the Wheeling
More informationOW LEE CASUAL FIRESIDE Q&A
Can you burn wood in the Casual Fireside pieces? No, these are not wood burning units. Casual Fireside Fire Pits are set-up to run on Propane but are easily converted to Natural Gas. Contact your local
More informationHYDRAPAK HH/HV BYPASS VALVE RETROFIT KIT INSTRUCTIONS
HYDRAPAK HH/HV BYPASS VALVE RETROFIT KIT INSTRUCTIONS REIMANN & GEORGER CORPORATION HOISTING PRODUCTS BUFFALO, NY P/N 6102--- 08/21/14 TABLE OF CONTENTS CHAPTER TITLE PAGE 1 SAFETY... 1 1.1 Introduction...
More information# RFP 50KW GENERATORS # RFP EQUIPMENT SHELTERS ADDENDUM #1
Return to: Dawson County Purchasing Department 25 Justice Way, Suite 2223 Dawsonville, GA 30534 #205-13 RFP 50KW GENERATORS #206-13 RFP EQUIPMENT SHELTERS ADDENDUM #1 Bid Closing Date: May 17, 2013 at
More informationFire hose, nozzles and hose appliances are among the most basic equipment used by firefighters.
Fire hose, nozzles and hose appliances are among the most basic equipment used by firefighters. Individual applications of these firefighting tools are sometimes misunderstood, resulting in incorrect and
More informationC402C / X toilets cassette toilets
C402C / X 0817 66 toilets cassette toilets C402C / X 0817 Colours available 1 Cover 2 Seat 32309 62 3 Pod 4 Magnet 5 Float box/foam 6 Float box guiding 32330 62 7 Reed switch housing WT Reed switch PCB
More informationNortech 30/55 Gal Units (Venturi) Data Sheet
Nortech / Gal (Venturi) Data Sheet & GALLON COMPLETE VACUUM UNITS Nortech & Complete Vacuum generate high vacuum lift and flow instantly and effectively. Designed to handle the toughest cleaning jobs with
More information100KTF1214 Rebuild Kit Series 100 Pump 1200KTF6725 Rebuild Kit Series 600, 1200B, 2400B
Group TC 100KTF1214 Rebuild Kit 01214-7 Series 100 Pump 1200KTF6725 Rebuild Kit 06725-3 Series 600, 1200B, 2400B 1200KTG8572 Rebuild Kit 18572-8 SD1202 & SD602 (MFG Date Earlier than 4404) 300KTF7794 Rebuild
More informationLooking forward to a great Fair
PO Box 3669 Durango, CO 81301 970-946-6697 This document has changed! Please read carefully before signing! We appreciate your interest in operating a food concession stand at the 2019 La Plata County
More informationHot Tips to Reduce your Fire Risks Justrite Mfg. Co.
Hot Tips to Reduce your Fire Risks 2009 Justrite Mfg. Co. Explaining Flash Point Liquid gives off flammable vapors Even a spark will ignite the vapor Flash Point Is: Lowest temperature at which sufficient
More informationOPERATING DIRECTIVE Number: D Aviation Authority Revised: 05/22/13
Page: 1 of 7 PURPOSE: To establish procedures to be followed by persons conducting non-commercial fuel dispensing and fuel storage at the Airports without a direct agreement with the Authority. For the
More informationIP3 IP4 LP7 IP5 IP6 IP2 IP1. Phase 1
? AMENDMENT No. SITUATED IN THE SW OF SECTION 8, T.S, R.W. OF THE TH P.M IP IP LP IP IP A C Phase APPROVED UNDER SEPARATE SUBMITTAL B IP IP INV IN=09.8 INV OUT=09.± MDP0-0080 No. REVISION BY Highlands
More informationAutomated Tiki Torch Installation Instructions
Automated Tiki Torch Installation Instructions Automated Tiki Torch with Poles (Exploded View) 14 Automated Tiki Head 6 8 Tiki Pole (Powder Coated Aluminum or Faux Bamboo Pole) 12 Base Pole (Powder Coated
More informationA Publication of. Ten Creative USes For Wet/Dry Vacs
A Publication of Ten Creative USes For Wet/Dry Vacs most creative JAN 2014 TEN CREATIVE USES 2 USES IN DEPTH 3 CLEAN OUT A BBQ PIT 3 PUMP OUT A FLOODED BASEMENT 4 FISHING PIPE 5 KITCHEN GOOPIES 5 UNCLOG
More informationSpill Containment Replaceable
Spill Containment /Poly The Series spill container features a corrosion free stainless steel primary container and is customizable for varied customer preferences. Rust-proof stainless steel primary containment
More informationInspection Check-off Sheet
Inspection Check-off Sheet Combustible vegetation that could create a fire hazard shall be removed from the area occupied by a tent or membrane structure, and from areas within 30 ft of. (Section 2404.20
More informationSTANDARD DETAILS & SPECIFICATIONS
STANDARD DETAILS & SPECIFICATIONS Spec. No. CFMO-SE1 Rev. Date: 10/24/12 Eff. Date: 08/23/90 Approved By: J. Saunders SUBJECT: Standard for Tents And Other Temporary Membrane Structures Page: 1 of 9 SCOPE
More informationClovis Fire Department
Clovis Fire Department Standard # 4.1 TENTS & CANOPIES Purpose The intent of this standard is to provide the minimum requirements needed to obtain a permit to erect tents or canopies. Scope This standard
More informationTent /Membrane Structure Permit Application
TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Tent /Membrane Structure Permit Application In accordance with the Code
More information2004 Spa Pre-Delivery Guide
2004 Spa Pre-Delivery Guide The guide to making your new Cal Spa installation easy. Duplication without written consent is strictly prohibited. This is for spas manufactured after May19, 2003 Revised July
More informationBuilding Permit Application
Building Permit Application Co-Owner Name Lot # Address City State Zip Phone (home) (cell) Contractor (if applicable) The above named co-owner hereby makes application to Cedar Shores Campground Condominium
More informationNon-pressurized vessels designed for the storage and transportation of liquid nitrogen
TR Non-pressurized vessels designed for the storage and transportation of liquid nitrogen 4Capacity of 7 to 100 litres 4Static holding time up to 180 days 46 year guarantee on the vacuum Insulated lid
More informationF I R E D E P A R T M E N T SANTA CLARA COUNTY
F I R E D E P A R T M E N T SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS SUBJECT: Tents, Canopies
More informationService Bulletin HHXDF5 Mechanical Ride-On Trowels LPG Hose Replacement
Service Bulletin HHXDF5 Mechanical Ride-On Trowels LPG Hose Replacement Product Group: Date Issued: Service Bulletin No. Ride-On Trowels Bulletin Type X Mandatory 2/6/6 TR20622 Models/Series Affected:
More informationSafety. BBA Compliance Kit Multi-Pro 5800 Turf Sprayer Model No Installation Instructions
BBA Compliance Kit Multi-Pro 5800 Turf Sprayer Model No. 41617 Note: Determine the left and right sides of the machine from the normal operating position. The BBA Compliance Kit is designed to meet German
More informationCARE, HANDLING & MAINTENANCE FOR ATTACK HOSE, LARGE DIAMETER HOSE (LDH), & SUPPLY HOSE
CARE, HANDLING & MAINTENANCE FOR ATTACK HOSE, LARGE DIAMETER HOSE (LDH), & SUPPLY HOSE North American Fire Hose Corporation is committed to providing the highest quality raw materials, unique design features,
More informationTherme storage water heater. Table of contents. Symbols used. Symbols used Symbol indicates a possible hazard. Installation instructions
Therme storage water heater Table of contents Symbols used... 8 Installation instructions Water supply... 9 Choice of location... 9 Installation of the Therme... 9 Fitting the draining and venting valve...
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
1. Authority Osceola County Department of Fire Rescue and TENT STANDARD This Standard operates under the authority of Osceola County, Florida Ordinance and State Statutes. 1.1 Scope This standard covers
More informationEXCELSIOR FIRE DISTRICT
EXCELSIOR FIRE DISTRICT Minnesota State Fire Code and the Excelsior Fire District Inspection Fire Safety & Code Requirements EXHIBITORS, VENDORS, CONCESSIONS, FOOD TRAILERS, TRUCKS, BOOTHS, AND TENTS UNDER
More informationtrue blue DEF Dispense Systems by Balcrank
true blue DEF Dispense Systems by Balcrank For over 100 years Balcrank has designed and manufactured quality fluid dispensing equipment systems, and outfits for the Automotive, Commercial and Industrial
More informationSPIEDR Deluge Structure Protection System. We appreciate the opportunity to support the protection of your valuable infrastructure.
WET FUEL WON T BURN Bob Swart, President Box 63, Quilchena, BC, V0E 2R0 fire.storm@shaw.ca June 29, 2016 Mr. Ken Bayers E-mail: ktbayers@gmail.com Phone # (604) 898 2803 SPIEDR Deluge Structure Protection
More informationA campsite area is defined from electric box to electric box to the road.
VI. CAMPGROUND 1. GENERAL RULES The campground was developed for the MEMBERS to use for recreation. It was not intended as a place to establish permanent residence. Family camping is available April 1
More informationCATALOG OF REPLACEMENT PARTS
CATALOG OF REPLACEMENT PARTS C24DA/GA-SERIES STEAMERS C24GA6 C24GA10 C24DA6 C24DA10 ML-138085 ML-138088 ML-152022 ML-152023 VULCAN-HART DIVISION OF ITW FOOD EQUIPMENT GROUP, LLC 3600 NORTH POINT BLVD.,
More informationAPPLICATION TO ERECT A TEMPORARY TENT OR CANOPY Fee: $147.00
Office of Fire Warden Fire Prevention Bureau Dale Skiles, Fire Warden Eric Holly, Deputy Fire Warden Randy Crook, Fire Marshal 1010 10 th Street Suite 3538 Modesto, CA 95357 Main Number: 209-552-3700 Fax:
More informationBlue Series Hot Melt Hose with RediFlext II Hanger System
Instruction Sheet P/N 1124594_01 Blue Series Hot Melt Hose with RediFlext II Hanger System Safety WARNING! Allow only personnel with appropriate training and experience to operate or service the equipment.
More informationMicro Brewery. can also supply piping, ladder and platform. We could also customize varied tanks according to customers requirements.
Micro Brewery We are capable of designing and producing wide range of stainless steel tank used in winery, such as wine fermentation tank with/ without filtering grid/ Sprinkler of pump-over system, storage
More informationFIRE REGULATIONS FOR OUTDOOR FESTIVALS CONCESSION BOOTHS (See Tents and Canopies Information Bulletin)
INFORMATION BULLETIN FIRE REGULATIONS FOR OUTDOOR FESTIVALS CONCESSION BOOTHS (See Tents and Canopies Information Bulletin) Code Reference: California Fire Code (CFC), 2001 Edition, Sections 2504 / 3201
More informationFBO-10 and FBO-14. Fuel Filter/Water Separator For High-Flow Applications. Product Features. Contact Information
FBO-0 and FBO-4 Fuel Filter/Water Separator For High-Flow Applications These versatile housings have three filter options to meet various requirements: a fuel filter/water separator, a silicone treated
More informationOperator's Manual. Model: RY10MK-PRO MPN: RA-MLT Gallon Direct Fire Melter Kettle Burner Model with Adjustable Flame-Out Valve
Operator's Manual Model: RY10MK-PRO MPN: RA-MLT-0009 10 Gallon Direct Fire Melter Kettle Burner Model with Adjustable Flame-Out Valve U.S. Patent No. 9,739,021 For Technical Support Please Visit www.rynoworx.com
More information2014 Utility Vehicle Sprayer Brochure
Effective Date: 01/01/2014 2014 Utility Vehicle Sprayer Brochure Agricultural & Professional Utility Vehicle Sprayers For 45 years, PBM Supply & Mfg., Inc. has been an innovative leader in the construction
More information9095 Overfill Prevention Valve Series
995 verfill Prevention Valve Series ( ( 2-inch 995AA 3-inch 995AA 995AA Aluminum Series - 2" Drop Tube 995AA2 AV 2 4 2 Direct fill 995AA32AVEVR 2 4 2 Remote fill ther Distinctions 995AA Aluminum Series
More informationEXCELSIOR FIRE DISTRICT
This checklist was created to help event planners prepare for the fire code and EFD requirements inspection. This checklist of for any event with exhibitors, vendors, concessions tents, food trucks, trailers,
More informationEXPLOSIONADO DE PARTES. Lavadoras de importación. Modelo: 7MGHW9100MW1
EXPLOSIONADO DE PARTES Lavadoras de importación Modelo: i Marca TOP AND CABINET Mexico S.A de C.V. 1/14 CMF R e f Marca Descripción C a n t TOP AND CABINET Numero de Parte 2 Top 1 8181641 3 CABINET 1 8181630
More informationPARTS LIST CHARGER 2022 ABLT
PARTS LIST CHARGER 2022 ABLT HEAD ASSEMBLY ITEM PART NO. DESCRIPTION QTY 101 5990731 SPRING CLIP PAD HOLDER SET INCLUDES: 1 101A 9120205 #8 X 1/2 PAN HEAD PHILLIPS SHEET METAL SCREW PACK OF 3 3 102 9121490
More informationFire's Edge Fire Pit/Fire Pit Inserts For (Automated) Model 100-A
Fire's Edge Fire Pit/Fire Pit Inserts For (Automated) Model 100-A OWNER S MANUAL / OPERATING AND MAINTENANCE INSTRUCTIONS For your safety: If you smell gas: 1. Shut off gas to the appliance 2. Extinguish
More informationSection B 5 Parts. 1. Introduction. Using the Illustrated Parts List. Parts B 5-1
Parts B - Section B Parts. Introduction To order parts, call the Nordson Customer Service Center or your local Nordson representative. Use the parts list, and the accompanying illustration, to describe
More information1260 West Riverside Drive rd Street SE Salem, VA Charlottesville, VA Toll Free: (866) Telephone: (434)
1260 West Riverside Drive 111 3 rd Street SE Salem, VA 24153 Charlottesville, VA 22902 Toll Free: (866) 653-8337 Telephone: (434) 293-4485 www.rainwatermanagement.com Version 1.0 Table of Contents Garden
More informationWE ARE MANUFACTURER!
WELCOME TO THE WORLD OF THE FIREFIGHTING BACKPACKS SINCE 2004 WE ARE MANUFACTURER! 10 Made in All our products are made in Czech Republic, in our factory and with our hands. Tradition We have more than
More informationTruDesign Aquavalve (Y Valve)
TruDesign Aquavalve (Y Valve) Legislation in many countries dictates the use of holding tanks near shore, or in defined areas. By installing a diverting valve (Y Valve), the user has the choice to divert
More informationCooking Booth Construction and Location (See Figure 1 and 2 for diagrams):
Page: 1 Of 9 Scope: This Standard shall apply to all cooking equipment, the including but not limited to: fryers, grills, BBQ s (both solid and LPG fuel supplied) and ovens. Use in or adjacent to booths
More informationLP Grill and Gas Hose
Tales from the Fox s Den Volume 1 7/2011 LP Grill and Gas Hose This seems to be a reoccurring theme on the forum and Internet about propane grills, quick disconnects, hoses, and what to do. First of all
More informationTent Policy & Procedures for Washington University in St. Louis
Tent Policy & Procedures for Washington University in St. Louis Table of Contents Tent Policy & Procedures for Washington University in St. Louis... 1 Notice... 2 Policy/Purpose... 2 General Information...
More informationJetCat USA 4250 Aerotech Center Way, Building G Paso Robles, CA 93446
Instruction manual 6V Kerosene Start System V2 (Part Number A1051-2) JetCat USA 4250 Aerotech Center Way, Building G Paso Robles, CA 93446 805-226-8700 Voice 805-226-8742 FAX www.jetcatusa.com 1 Content
More informationSection B 5 Parts. 1. Introduction. Using the Illustrated Parts List. Parts B 5-1
Parts B - Section B Parts. Introduction To order parts, call the Nordson Customer Service Center or your local Nordson representative. Use the parts list, and the accompanying illustration, to describe
More informationS.A.Q s: What are questions I should ask when contemplating into the design, specifying, or purchasing a fire pit?
1 S.A.Q s: What are questions I should ask when contemplating into the design, specifying, or purchasing a fire pit? 1. What is the difference between the fuel types? a) Natural Gas (NG): There is an immediate
More informationWRANGLER 1710AB, 2010AB
WRANGLER 1710AB, 2010AB WIRING DIAGRAM ITEM PART NO. DESCRIPTION QTY 1 1393251 WIRE ASSEMBLY - CIRCUIT BREAKER TO BRUSH SWITCH 1 2 1393261 WIRE ASSEMBLY - CIRCUIT BREAKER TO VACUUM SWITCH 1 3 1393271 WIRE
More informationGas Conversion Kits and Instructions
Gas Conversion Kits and Instructions INSTALLATION FORM RGM 432/433-GC (Version D.1) Obsoletes Form RGM 432/433-GC (Version D) APPLIES TO: Model FT and Model SFT All gas conversion must be done by a qualified
More informationArticle 10 Hotels and Motels
Article 10 Hotels and Motels 41001. Definitions. 41002. Compliance. 41003. Guest Rooms. 41004. Bedding. 41005. Water Supply. 41006. Ice. 41007. Sewage Disposal. 41008. Plumbing. 41009. Food Service. 41010.
More informationQuality Consistency Reliability.
WAND CATALOG Quality Consistency Reliability. Each and every tool that EDIC sells is rigorously tested with high pressure solution at EDIC s factory in Los Angeles before it is approved for shipment. EDIC
More informationPARTS LIST eforce Burnisher
PARTS LIST eforce Burnisher HEAD ASSEMBLY ITEM PART NO. DESCRIPTION QTY 101 6496721 MOTOR 36 VOLT, 2100 RPM, 3.6HP [see pages 16,17] 1 102 9121410 5/16 EXTERNAL STAR LOCK WASHER PACK OF 10 2 103 6492051
More informationClay & Bailey Mfg. Co.
Clay & Bailey Mfg. Co. VENTING GUIDE & PRODUCT CATALOG for Aboveground Storage Tanks new products! new products! Emergency Vents NOW UL Listed! Emergency Vents NOW UL Listed! 9/12 Clay & Bailey Mfg. Co.
More informationGO TO INDEX NEXT PAGE B&K PRODUCT SPECIFICATIONS B & K. Gauge CALL: BK-TANK FAX: B&K TANK GAUGE COMPANY
GO TO INDEX NEXT PAGE B&K PRODUCT SPECIFICATIONS B&K B & K Tank 74 75 Gauge 73 71 72 Company 70 69 SINCE 1946 CALL: 1-800-4BK-TANK FAX: 908-722-8585 B&K TANK GAUGE COMPANY division of Summit Systems Inc.
More informationThe Right Choice NEW. Safety Containers Protection PLUS Performance.
NEW The Right Choice Safety Containers Protection PLUS Performance The Right Choice Protection plus advanced performance when handling volatile fuels, chemicals, and solvents NEW Innovative new features
More informationThis Guide will tell you everything you need to know about the delivery and installation of your new QCA Spa. Box Merchant Pre-Delivery Guide
This Guide will tell you everything you need to know about the delivery and installation of your new QCA Spa. Box Merchant Pre-Delivery Guide Important Information Please make a record of the following
More informationDUPLEX STRAINERS BULLETIN NO KECKLEY COMPANY 3400 Cleveland Street P.O. Box 67 Skokie, Illinois 60076
Distributed By: M&M Control Service, Inc. www.mmcontrol.com/keckley.php 800-876-006 847-6-066 BULLETIN NO. 9400- DUPLEX STRAINERS Shown with Optional Differential Pressure Indicator KECKLEY COMPANY 400
More informationMODELS: 440 SM & 440 SMSS
Most Dependable Fountains, Inc. OPERATIONS MANUAL MODELS: 440 SM & 440 SMSS Most Dependable Fountains, Inc 5705 Commander Drive Arlington, TN 38002 800-552-6331 FOUNTAINS, MOST DEPENDABLE FOUNTAINS, INC.
More informationVFR Parallel Flow, Fan-Powered, VAV Terminals
VFR Parallel Flow, Fan-Powered, VAV Terminals Model VFR construction features Galvanized-steel casing withstands 125-hour, salt-spray test per ASTM B-117 All unit configurations listed with ETL for safety
More informationTECHNICAL SUPPORT HOT LINE HOURS: 7:30-3:30
TECHNICAL SUPPORT HOT LINE 1-800-526-0725 HOURS: 7:30-3:30 TO: Service Providers BULLETIN No: 0102-1 FROM: SUBJECT: BOB VAN WYCK Technical Support Manager Burner Pilot Tube Replacement DATE: Feb 1, 2001
More informationUltraflow Compact Housing and Winter Kit
Ultraflow Compact Housing and Winter Kit Operating instructions Page 2 Installation instructions Page 8 To be kept in the vehicle! Comfort on the move Ultraflow Compact Housing and Winter Kit 1 Compact
More informationInstructions for Converting Range to Operate on Liquefied Petroleum Gas
INSTALLATION AND SERVICES MUST BE PERFORMED BY A QUALIFIED INSTALLER IMPORTANT: SAVE INSTRUCTION MANUAL FOR THE LOCAL INSPECTOR S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE This conversion
More informationTent Policy & Procedures for Danforth, North, West and South Campuses at Washington University in St. Louis
Tent Policy & Procedures for Danforth, North, West and South Campuses at Washington University in St. Louis NOTICE: No tents or canopies will be allowed on University properties unless authorized by the
More informationFire Pit Tables. Installation Instructions. Sierra, San Juan, Grandstone, Rivers Edge, Pike s Peak. 1 P a g e
Fire Pit Tables Sierra, San Juan, Grandstone, Rivers Edge, Pike s Peak Installation Instructions 1 P a g e Contents Contents..2 Required Tools...3 Placing the Table.. 4 Gas Connection..5 Igniter Installation....6
More informationget connected with Bradford fittings & valves Bradford Company, Inc
get connected with Bradford fittings & valves Bradford Company, Inc. 800.789.1718 www.bradfordfittings.com Bradford your top quality, sanitary stainless steel fittings & valves manufacturer serving you
More informationAutomatic shut-off nozzle
Page 1 of 5 APPLICATION OPW 11AL Series for Automobile Refuelling 11AL Nozzles are designed for today s self serve customer, with safety and the environment in mind. Trim, lightweight and easy to use,
More informationPARTS LIST MODEL M-1 - PIG
PARTS LIST MODEL M-1 - PIG FAN HOUSING ASSEMBLY ITEM PART NO. DESCRIPTION QTY 101 1090601 LABEL KIT - M-1 PIG 1 102 2590019 SWIVEL COUPLING ASSEMBLY - INCLUDES: 1 102A 2590111 HOSE COUPLING GASKET 1 103
More informationAERO TEC LABORATORIES
IMPORTANT INFORMATION FROM ATL SAFETY FUEL CELLS FOR HISTORIC RACE CARS, CLASSIC BOATS AND VINTAGE AIRCRAFT 1.) REPLACING AN OLD OR DETERIORATED FUEL BLADDER a.) Remember, modern fuel bladder materials
More informationChip Vac Chip Vac Vacuums chips directly into an open-top drum with no moving parts! What Is The Chip Vac? Why The Chip Vac? Watch the video!
Chip Vac Chip Vac Vacuums chips directly into an open-top drum with no moving parts! What Is The Chip Vac? EXAIR's Chip Vac picks up dry or wet chips and delivers them directly to an ordinary open-top
More informationGASTRO-INTESTINAL (ENTERAL)
GASTRO-INTESTINAL (ENTERAL) 139 B A C D Gastrostomy Feeding Tubes Tri-Funnel Replacement Gastrostomy Tube Green inflator cuff, sterile. Bard 12 French, 5 cc balloon, white. #000712 (A) 043120 Each 14 French,
More informationAMS Gas Vapor Probe Systems (GVP)
AMS Gas Vapor Probe Systems (GVP) AMS GVP systems are equipped with two different styles of 5/8in OD extensions: solid tile probe extensions, and hollow GVP rods. Extendable tile probe extensions are solid
More informationYour Neighborhood Hardware Store. was $49.99 Universal Ratcheting Wrench Set 72 tooth with 5 swing for better performance in tight areas
$59 $40 was $. 20V MAX Lithium-ion Cordless Sweeper Up to 130mph air velocity, includes battery 705303 Your Neighborhood Hardware Store $1 was $2.49 5Pk Yard Waste Bags 30 Gal capacity and is self-standing,
More informationDUPLEX STRAINERS 800-KECKLEY ( ) BULLETIN NO / FAX: 847/ WEB SITE:
BULLETIN NO. 9400- DUPLEX STRAINERS 800-KECKLEY (800-2-9) 847/674-8422 FAX: 847/674-206 E-MAIL: SALES@KECKLEY.COM WEB SITE: WWW.KECKLEY.COM NO QUESTION. WE HAVE THE ANSWERS. Shown with Optional Differential
More informationET600 PARTS LIST MODELS (100), (100H), (400H)
ET600 PARTS LIST MODELS 5605 (00), 5605 (00H), 5605 (00H) 7/0 revised 8/06 FORM NO. 560585 REV F PARTS LIST TABLE OF CONTENTS DESCRIPTION PAGE Base System - 00H... - Base System - 00H... -5 Base System
More information