AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to: TORO ALUMINUM SERIES/MODEL: Series 8200 Curtain Wall TYPE: Glazed Wall System Report No: Report Date: E7666.01-116-45 05/15/15 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129
AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to: TORO ALUMINUM 330 Applewood Crescent Concord, ON L4K 4V2 Canada Report No: E7666.01-116-45 Report Date: 05/15/15 Simulation Date: 05/15/15 Project Summary: Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted by Toro Aluminum to provide U-Factor and Solar Heat Gain Coefficient thermal performance ratings on the Series 8200 Curtain Wall Glazed Wall System. The thermal performance ratings were determined in accordance with AAMA 507-12, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Building. Reference Documents: AAMA 507-12, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Buildings ANSI/NFRC 100-2014, Procedure for Determining Fenestration Product U-Factors ANSI/NFRC 200-2014, Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence Simulation Specimen Description: Series/Model: Series 8200 Curtain Wall Type: Glazed Wall System Frame Material: Aluminum Thermally Broken Framing System Material Finish: Painted Aluminum Specimen Size: 2000mm wide by 2000mm high (78-3/4" by 78-3/4") Configuration: Two vision lites separated by one intermediate vertical Drawing Reference: Toror Aluminum Drawing Series 8200 Hor./Vert. Details, dated 03/26/15 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129
E7666.01-116-45 Page 2 of 10 Toro Aluminum Series 8200 Curtain Wall - Glazed Wall System System U-Factor vs. Percentage of Vision Area 0.70 0.65 0.60 COG U-Factor 0.55 0.48 0.50 0.46 0.44 0.42 0.40 0.38 0.36 0.34 0.32 0.30 0.28 0.26 0.24 0.45 0.40 0.35 0.30 System U-Factor (Btu/h ft 2 ºF) 0.22 0.20 0.18 0.16 0.14 0.12 0.10 0.25 0.20 0.15 95 90 85 80 75 0.10 70 Vision Area / Total Area (%) Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG) with Aluminum Spacer
E7666.01-116-45 Page 3 of 10 Toro Aluminum Series 8200 Curtain Wall - Glazed Wall System System SHGC vs. Percentage of Vision Area COG SHGC 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 System SHGC 0.05 0.05 95 90 85 80 75 0.00 70 Vision Area / Total Area (%) System VT vs. Percentage of Vision Area COG VT 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 System VT 95 90 85 80 75 0.00 70 Vision Area / Total Area (%)
E7666.01-116-45 Page 4 of 10 Toro Aluminum Series 8200 Curtain Wall - Glazed Wall System Size Specific U-Factor Matrix* Glazing Option Center of Glass U-Factor Overall U-Factor 1 0.48 0.54 2 0.46 0.52 3 0.44 0.51 4 0.42 0.49 5 0.40 0.48 6 0.38 0.46 7 0.36 0.44 8 0.34 0.43 9 0.32 0.41 10 0.30 0.39 11 0.28 0.38 12 0.26 0.36 13 0.24 0.34 14 15 16 17 0.22 0.20 0.18 0.16 0.33 0.31 0.28 0.27 18 0.14 0.25 19 0.12 0.23 20 0.10 0.22 Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG) with Aluminum Spacer
E7666.01-116-45 Page 5 of 10 Toro Aluminum Series 8200 Curtain Wall - Glazed Wall System Size Specific SHGC Matrix* Size Specific VT Matrix* Center of Glass SHGC Overall SHGC Center of Glass VT Overall VT 0.75 0.68 0.75 0.68 0.70 0.64 0.70 0.63 0.65 0.59 0.65 0.59 0.60 0.55 0.60 0.54 0.55 0.50 0.55 0.50 0.50 0.46 0.50 0.45 0.45 0.41 0.45 0.41 0.40 0.37 0.40 0.36 0.35 0.32 0.35 0.32 0.30 0.28 0.30 0.27 0.25 0.23 0.25 0.23 0.20 0.19 0.20 0.18 0.15 0.14 0.15 0.14 0.10 0.10 0.10 0.09 0.05 0.05 0.05 0.05 *Size Specific U-Factor, SHGC, and VT Matrices are based on the standard Glazed Wall System specimen size of 2000mm wide by 2000mm high (78-3/4" by 78-3/4"). This represents 90.7% Vision Area / Total Area.
E7666.01-116-45 Page 6 of 10 Option No. 1 2 3 4 5 6 7 8 9 COG U-Factor 0.48 0.46 0.44 0.42 0.40 0.38 0.36 0.34 0.32 COG Temperature 43.7 44.8 45.8 46.8 47.9 48.9 50.0 51.0 52.0 Cross Section Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Head L. Jamb R. Jamb Mullion Sill Frame Height Frame U-Factor Vision Area Data Edge U-Factor 70% Vision Area 23.20" by Total Product U-Factor NFRC 100-2010 78.74" 95% Vision Area 148.43" 23.20" 78.74" 148.43" 1.4188 1.0966 0.4776 0.4816 0.7082 0.5414 0.4988 1.1012 0.4818 2.5952 1.0989 1.4400 1.4170 0.4817 0.4596 0.4636 0.6963 0.5248 0.4817 2.5952 1.0942 1.0988 1.0965 1.4384 0.4675 0.4677 0.4676 0.4456 1.4154 0.4497 0.6845 0.5082 0.4646 2.5952 1.0920 1.0966 1.0943 1.4368 0.4534 0.4537 0.4536 0.4317 1.4138 0.4362 0.6728 0.4918 0.4476 2.5952 2.5952 1.0898 1.0945 1.0922 1.4354 1.4123 1.0877 1.0924 1.0900 0.4397 0.4401 0.4399 0.4181 0.4223 0.4257 0.4260 0.4259 0.6610 0.4752 0.4304 2.5952 1.4339 1.4108 1.0857 1.0904 1.0881 0.4042 0.4089 0.4121 0.4125 0.4123 0.6495 0.4586 0.4133 1.4327 1.4092 1.0835 0.3907 0.3951 0.3982 0.6377 0.4420 0.3959 1.0882 0.3987 2.5952 1.0858 0.3984 1.4311 0.3769 1.4082 0.3818 0.6264 0.4255 0.3787 1.0819 1.0867 0.3847 0.3852 2.5952 1.0843 1.4302 1.4069 1.0801 1.0848 0.3850 0.3635 0.3683 0.3711 0.3717 0.6149 0.4089 0.3613 2.5952 1.0825 1.4291 0.3714 0.3500 by by
Option No. COG U-Factor COG Temperature Cross Section Frame Height Frame U-Factor Vision Area Data Edge U-Factor Total Product U-Factor E7666.01-116-45 Page 7 of 10 70% NFRC 95% Vision Area 100-2010 Vision Area 23.20" 78.74" 148.43" by by by 23.20" 78.74" 148.43" 10 0.30 53.1 Head 1.4058 0.3550 0.6036 0.3923 0.3439 L. Jamb 1.0784 0.3578 R. Jamb 1.0831 0.3583 Mullion 2.5952 1.0807 0.3580 Sill 1.4281 0.3367 11 0.28 54.2 Head 1.4048 0.3417 0.5923 0.3757 0.3264 L. Jamb 1.0767 0.3443 R. Jamb 1.0815 0.3449 Mullion 2.5952 1.0791 0.3446 Sill 1.4272 0.3234 12 0.26 55.2 Head 1.4037 0.3285 0.5810 0.3590 0.3089 L. Jamb 1.0751 0.3309 R. Jamb 1.0799 0.3316 Mullion 2.5952 1.0775 0.3313 Sill 1.4262 0.3101 13 0.24 56.3 Head 1.4028 0.3153 0.5698 0.3424 0.2915 L. Jamb 1.0736 0.3176 R. Jamb 1.0784 0.3183 Mullion 2.5952 1.0760 0.3180 Sill 1.4254 0.2969 14 0.22 57.3 Head 1.4021 0.3021 0.5586 0.3258 0.2740 L. Jamb 1.0723 0.3043 R. Jamb 1.0771 0.3050 Mullion 2.5952 1.0747 0.3046 Sill 1.4248 0.2837 15 0.20 58.4 Head 1.4012 0.2890 0.5475 0.3092 0.2563 L. Jamb 1.0709 0.2910 R. Jamb 1.0758 0.2918 Mullion 2.5952 1.0733 0.2914 Sill 1.4242 0.2706 16 0.18 59.5 Head 1.3020 1.3540 0.2640 0.5126 0.2849 0.2347 L. Jamb 1.3020 1.0056 0.2650 R. Jamb 1.0103 0.2657 Mullion 2.5952 1.0079 0.2653 Sill 1.3774 0.2455 17 0.16 60.6 Head 1.3020 1.3528 0.2508 0.5014 0.2680 0.2167 L. Jamb 1.3020 1.0038 0.2517 R. Jamb 1.0085 0.2524 Mullion 2.5952 1.0061 0.2521 Sill 1.3764 0.2323 18 0.14 61.7 Head 1.3020 1.3533 0.2366 0.4901 0.2512 0.1989 L. Jamb 1.3020 1.0032 0.2373 R. Jamb 1.0079 0.2381 Mullion 2.5952 1.0055 0.2377 Sill 1.3770 0.2183
Option No. COG U-Factor COG Temperature Cross Section Frame Height Frame U-Factor Vision Area Data Edge U-Factor Total Product U-Factor E7666.01-116-45 Page 8 of 10 NFRC 95% Vision Area 100-2010 Vision Area 23.20" 78.74" 148.43" by by by 23.20" 78.74" 148.43" 19 0.12 62.8 Head 1.3020 1.3523 0.2233 0.4788 0.2343 0.1808 L. Jamb 1.3020 1.0015 0.2239 R. Jamb 1.0063 0.2247 Mullion 2.5952 1.0039 0.2243 Sill 1.3762 0.2050 20 0.10 63.9 Head 1.3020 1.3515 0.2100 0.4676 0.2174 0.1627 L. Jamb 1.3020 1.0000 0.2104 R. Jamb 1.0049 0.2112 Mullion 2.5952 1.0024 0.2108 Sill 1.3756 0.1917 70%
E7666.01-116-45 Page 9 of 10 Intertek-ATI will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Intertek-ATI for the entire test record retention period. The test record retention end date for this report is May 15, 2019. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the product simulated. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: SIMULATED BY: REVIEWED BY: Kristen L. Louder Senior Simulation Technician Kevin S. Louder Project Engineer KLL:KLL E7666.01-116-45 Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Drawings and Bills of Material (9)
E7666.01-116-45 Page 10 of 10 Revision Log Rev. # Date Page(s) Revision(s).01R0 05/15/15 All Original Report Issued to Toro Aluminum
All drawings and Bills of Material used in simulating this product are enclosed in this Appendix. Appendix A E7666.01-116-45