SPECIAL EVENTS --- TENTS --- COOKING

Similar documents
USE OF TENTS Guide. Frederick County Fire and Rescue Services Division. Office of the Fire Marshal

Tents & Membrane Structures Information Packet

SUNY GENESEO ENVIRONMENTAL HEALTH AND SAFETY

Inspection Check-off Sheet

Cooking Booth Construction and Location (See Figure 1 and 2 for diagrams):

FIRE REGULATIONS FOR OUTDOOR FESTIVALS CONCESSION BOOTHS (See Tents and Canopies Information Bulletin)

Tent Policy & Procedures for Washington University in St. Louis

Marin County Fire Department. Fire Protection Standard 119. Tents and Awnings

Tent Policy & Procedures for Danforth, North, West and South Campuses at Washington University in St. Louis

Outdoor Tent Permit Requirements

Temporary Structure Permit Guide

TENTS, CANOPIES AND TEMPORARY MEMBRANE STRUCTURES

CODE SUMMARY TENTS AND OTHER MEMBRANE STRUCTURES

Permit Application Requirements For Temporary Tents, and Membrane Structures

Clovis Fire Department

Tents and Air Supported Membrane Structures

APPLICATION TO ERECT A TEMPORARY TENT OR CANOPY Fee: $147.00

Tent /Membrane Structure Permit Application

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

APPLICATION FOR TENTS/INFLATABLES

Osceola County Department of Fire Rescue and Emergency Medical Services

EXCELSIOR FIRE DISTRICT

Simplified Guide to Fire Prevention - Exhibition. March 2014 issue

Guidelines for Tents/Canopies on Campus

TENT AND CANOPY POLICY

Temporary Structure/Use Checklist

F I R E D E P A R T M E N T SANTA CLARA COUNTY

STANDARD DETAILS & SPECIFICATIONS

- Tents larger than 10 x 12 require a permit from Santa Rosa Island Authority and may require a permit from Escambia County, for inquiry.

TENT PERMIT APPLICATION AND CHECKLIST

Required. When application not signed by owner Permit Fee V As per Fee By-law

SFM HCD DSA OSHPD T-24 T-19* 1 2 1/AC AC SS

EXCELSIOR FIRE DISTRICT

Vendor Requirements Bikes Blues & BBQ

Looking forward to a great Fair

Amber Long. Chief Pomeroy,

TWO BURNER STAINLESS STEEL PROPANE STOVE

For Outdoor Use Only!

MEMORANDUM Thomas J. Kaminski

For Outdoor Use Only!

MODEL DCC DOUBLE WALL CHIMNEY CONNECTOR

Bodega Bay Fisherman s Festival Food Vendor Information/Application

Commander U. S. Coast Guard Eighth Coast Guard District

State of California Health and Human Services Agency California Department of Public Health

COMMUNITY EVENTS PERMIT APPLICATION. Address to which Permit can be mailed:

MODEL DCC DOUBLE WALL CHIMNEY CONNECTOR

Camping Chef Folding Elite Camping Chef Folding Compact Camping Chef Folding

Section 61 Recreational Vehicle Park / Campground (Bylaw No. 2012/10)

EXCEL ULTRABlack FS 6 Clearance Connector INSTALLATION AND MAINTENANCE INSTRUCTIONS

BOOTH RULES AND REGULATIONS

This document has changed! Please read carefully before signing!

SINGLE BURNER STOVE IMPORTANT OPERATING INSTRUCTIONS COOKING & STORAGE POSITION PARTS IDENTIFICATION

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS JUMBO/JUMBO SLIMLINE LOG SYSTEMS

Assembly Instructions & User s Manual 26 Florence Folding Leg Fire Pit

Installer: Leave This Manual with Consumer Consumer: Save this Manual for Future Reference

Flammable and Combustible Liquids. OSHA Office of Training and Education 1

Section 8: Supplements

PATHFINDER CAMP SAFETY INSPECTION FORM

Published March 2016 PARK RULES

Title 09 Department of Labor, Licensing, and Regulation Subtitle 12 Division of Labor and Industry

Lit Table Top Firepit Bio-Ethanol Fireplace. User Manual. Model: GF301650

Style # Laguna Propane Tank Cover Owner s Manual

University of California, Davis TEMPORARY FOOD FACILITY APPLICATION THIRD PARTY VENDOR

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG FIRE PIT SERIES ONLY

Seasonal Camping Agreement Beavermead Family Campground 2018

CARTARP CARTARP INSTRUCTIONS INSTRUCTION INDEX YOUR KELTY CARTARP SHOULD INCLUDE: Before you Start 2-5 Pitching your CarTarp 6-11 Notes 11 Warranty 12

INSTRUCTIONS MANUAL CAST IRON STOVE

St. Patrick s Day Parade and Festival

Standard Ignition 2014 The Coleman Company, Inc colemanaustralia.com.au IMPORTANT

Business Name: Contact Name: Website: Address: Contact Phone #:

FACT SHEET Program: Lab Fire Safety

FOOTBALL TAILGATE POLICY

VENDOR PACKET. pecanstreetfestival.org SPRING FESTIVAL

Performer Application/Contract

LEGAL REQUIREMENTS FOR STORING AND TRANSPORTING FLAMMABLES AND CHEMICALS

EB300. Ethanol Burner. User s Manual Installation Instructions

Garden Party 13ft X 13ft 12ft 9in Wide x 12ft 9in Deep x 6ft3in Side Height / 10ft4in Center Height

YELLOWSTONE YELLOWSTONE INSTRUCTIONS INSTRUCTION INDEX YOUR KELTY TENT SHOULD INCLUDE:

Fire's Edge Fire Pit/Fire Pit Inserts For (Automated) Model 100-A

Fire safety in camping sites. CFPA-E Guideline No 20:2012 F

S.A.Q s: What are questions I should ask when contemplating into the design, specifying, or purchasing a fire pit?

Assembly Instructions

Annual Fire Safety Report for Indiana University Year , Bloomington Campus

ANNEX 2. RESOLUTION MSC.308(88) (adopted on 3 December 2010)

t420 Barbecue Assembly Manual

TRAIL DOME TRAIL DOME INSTRUCTIONS INSTRUCTION INDEX YOUR KELTY TENT SHOULD INCLUDE: Before you Start 2-4 Pitching your Tent 5-7 Notes and Warranty 8

CARSON CITY AIRPORT HANGAR INSPECTION POLICY

OWNER S MANUAL 10x10 SUN SHELTER WITH NETTING

CITY OF MURFREESBORO BOARD OF ZONING APPEALS

SECTION 5 AERONAUTICAL ACTIVITIES

Riley-Jacques Farmstead 9100 Riley Lake Road, Eden Prairie, MN 55347

Installation Guide. LPKPDR - Universal LP Conversion Kit for Professional & Designer Ranges/Rangetops. Viking Range, LLC.

Hampton Gazebo. ITEM# L-GZ098PST-1B Assembly Instruction

ECLIPSE AIR HEAT BURNERS Series AH-O & TAH-O

OCTOBER 19-21, 2018 CAMP GENEVA FRUITLAND PARK, FL

9966 Series. Propane Stoves. Instructions for use. INSTASTART Electronic Ignition Standard Ignition. Camp Stove

S420 Barbecue Assembly Manual

CFS FACT SHEET - CAMPFIRES & BARBECUES

Sportster II Dual Fuel Stove

2 Burner ASSEMBLY MANUAL

Transcription:

Fire Prevention: (519)-763-8111 Admin: (519) 824-6590 Fax: (519) 824-2147 SPECIAL EVENTS --- TENTS --- COOKING 1. MEANS OF EGRESS Adequate means of egress are required and provided so that such exit facilities are unobstructed and lead to an approved open space. Fire Safety Plans (events in tents over 50 people) must be submitted to this department 15 days prior to the event. Eg: If fencing is used, exits shall be provided to allow the occupants to leave the immediate area. 2. USE OF TENTS When tents are used they shall be certified that the material used has been made fire retardant by treatment in accordance with the Standard Methods of Fire Tests for Flame Resistant Textiles and Films. Ref. NFPA 701, NFPA 705 or CAN/ULC S-109-M. Polyester and nylon type materials are not permitted to be used to cooking beneath or hanging decorative lights. a) Electrical equipment shall be maintained and operated in a safe manner. IF in doubt contact the Electrical Safety Authority. 1-877-372-7233 b) A tent shall not be erected so that it covers more than 75% of the available open space or be erected closer than three meters () to other structures, fences or obstructions. c) Hay, stray, shavings or similar combustible materials other than those necessary for the daily feeding and care of animals, shall not be permitted within a tent accessible to the public. d) Smoking, fireworks, cooking equipment or open flame of any kind shall not be permitted in a tent while it is occupied by the public. COOKING WITHIN TENTS a) Cooking appliances covered by this guideline include, but is not limited to, grills, ranges, ovens, fryers, broilers, griddles, etc, which use solid, liquid or gas fuels. (exception: the use of Sterno for the warming of food). Technical Standards and Safety Authority ( TSSA) inspections must be arranged by organizers for all vendors utilizing fuel fired cooking appliances. 1-877-682-8772 b) All tents and canopies in which cooking operations are performed shall be separated from all other tents, canopies or buildings by at least six meters (). This measurement shall be from tents/canopy stakes to tent/canopy stakes. Clearance to combustibles within the tent must be a minimum one point two metres (1.2m) or as stated on appliance label.

c) Any tent or canopy in which cooking operations are performed shall be used for cooking ONLY. Tents or canopies must meet NFPA 701, NFPA 705 standard or CAN/ULC-S109. A Current Certificate is required upon request that the material meets or exceeds these requirements. COOKING WITH IN TENTS OR UNDER CANOPIES MUST BE APPORVED BY THE FIRE PREVENTION DIVISION. No cooking will be permitted in an enclosed tent. Exception: A tent or canopy may be used for dining purposes in addition to cooking if the following requirements are satisfied: A. Any grease-producing appliance shall have a Type I hood system. B. A UL 300 compliant fire suppression system shall be provided within the hood system. C. The fire suppression system shall have a current inspection certification. D. A Class K fire extinguisher shall be within ten meters (10m) of all cooking appliances. E. Adequate air flow must be provided to prevent the build up of Carbon monoxide d) Occupant load - number of persons allowable shall be posted, and conform to table 3.1.16.A of the Building Code. e) A person shall be employed to watch for fires in tents occupied by the public where the facilities are designed to accommodate more than a 100 persons. f) Generators and other internal combustion power sources shall be separated from any tent, canopy or building by at least six metres (). g) All flammable/combustible liquids shall be safely and properly stored. This storage shall be at least a fifteen meters (15m) from any tent, canopy or building. h) Outdoor cooking, (not within a tent or canopy), that produces sparks, flame or grease- laden vapours shall be done at least six meters () from any tent, canopy or building. 3 PORTABLE FIRE EXTINGUISHERS Shall be provided and positioned so as to be accessible without exposing the operator to undue risk. Minimum size shall have a 3A10BC rating. A Class K fire extinguisher shall be within ten meters (10m) of all cooking appliances that produce grease-laden vapours. (40 BC extinguisher may be approved) Extinguishers MUST have a current tag certifying maintenance within last 12 months. All further inquiries with respect to special events and in the interest of fire safety shall be directed to the Fire Prevention Division at 519-763-8111.

NON COOKING TENTS COOKING TENTS Non cooking tents (10 Feet) From all structures BBQs (10feet) From rated tents (10 feet) Fryers (10 Ft) Cooking Tent with Fire Resistive Rating (20 feet) from all structures Non rated tent no cooking Non- rated NO tent COOKING WITHIN A TENT THAT HAS SEATING OR USED AS AN ASSEMBLY OCCUPANCY Rated tent with BBQ BBQ Trees or other combustible structures Main Tent Rated tent cooking Deep fryer BBQ Trees combustible material NOTES All food vendors must submit a list and picture of equipment being used at event at least 21 days prior to event. TENTS must have a NFPA 701, NFPA 705 standard or CAN/ULC-S109 Fire Resistive Rating label affixed to the tent. Tents with deep fryers --- must install a fixed non-combustible weather shield at least 40 inches above the fryer. No fryers are permitted inside a rate tent unless the shield is installed. You must install the fryer on a wood or concrete base so that the fryer is completely stable. K type fire extinguishers must be present when fryers are used. BBQs must be approved and propane cylinders securely fastened. This includes any spare cylinders. Vehicles with Deep Fryers enclosed in a self-contained unit require a hood range and fixed extinguishing system. All grease filters/grease removal devices shall be listed by an accredited listing agency - i.e. UL, ULC, ETL etc. The exhaust air volume for the hood shall be of a sufficient level to provide for the capture and removal of grease laden cooking vapors Revised July 2013

BBQ under tent BBQ to close to combustible trees Propane not secured Deep fryer no protection Cooking equipment under tent

Approval Label MUST be affixed to Tent Requirements to be on label.